SP 500 W 48
Power Supply Unit
Specifications | |
Type | SP 500 W 48 |
INPUT | |
AC input voltage range | 88 ... 264 V AC |
DC input voltage range | 124 ... 370 V DC |
Frequency range | 47 ... 63 Hz |
AC input current (at 230 V) | 3.5 A |
AC inrush current (at 230 V) | 36 A |
Efficiency | 87 % |
OUTPUT | |
DC voltage | 48 V |
Voltage adjust range | 41 ... 56 V |
Voltage tolerance | +/- 1.0 % |
Ripple and noise | max. 300 mVpp |
Rated current | 10 A |
Current range | 0 ... 10 A |
Rated power | 480 W |
Setup time, rise time | 1500 ms, 50 ms at full load (at 230 V AC) |
Hold time (typ.) | 24 ms at full load (at 230 V AC) |
PROTECTION | |
Over voltage | 57.6 ... 67.2 V (Protection type: Hiccup mode, recovers automatically after fault condition is removed) |
Withstand voltage | I/P-O/P: 3.0 kV AC |
I/P-F/G: 1.5 kV AC | |
O/P-FG: 0.5 kV AC | |
Dimensions (mm) | 170 x 120 x 93 |
I/P = Eingang (Input), O/P = Ausgang (Output), | |
Features
- Universal AC input / Full range
- Built-in active PFC function, PF>0.95
- Built-in remote ON-OFF control
- Forced air cooling by built-in DC fan
- Protections:Short circuit/Over load/Over voltage/Over temperature
Dimensions
- Specifications subject to change without notice -